Fire-rated and specialty doors for export projects
Start with the opening. We match the door and the documents.
Jieyue supplies steel fire doors, fire shutters, fire-rated windows and non-fire-rated clean room and industrial doors to contractors and importers. Send your door schedule and we confirm, opening by opening, what we can supply and which test evidence applies.
UL certificates cover one model today — steel door KYFD001S. Ratings for every other door are confirmed per project, in writing, before production.
Certificate facts
- UL 10B · model KYFD001S
- Up to 3 hours · masonry wall
- Single-swing, steel-covered composite door
- Every other rating confirmed per project
Four things we need to know about each opening
A fire door is chosen by the opening it protects, not by a catalogue name. Answer these four questions for each opening and we can tell you what we can supply.
What the building is used for
Hospital, office, hotel, warehouse, plant room or residential block — and where the door sits: stair, corridor or plant room. The use decides which code requirements apply.
How big the opening is
Opening width × height in mm or inches, single leaf or pair, and the wall it sits in: masonry, concrete or a lightweight partition.
How long it must resist fire
The rating on your drawings — for example 20, 45, 60 or 90 minutes, or 3 hours — and the test standard your specification names.
Where it will be installed
Destination country and who approves the door: the local building authority, civil defence or a building certifier. Their rules decide which documents count.
Also useful: glazing or louvres, hardware, frame type, finish, quantity and the date you need the doors on site.
Fire-rated product lines
Fire ratings and test evidence belong to a specific model and construction, not to a whole product line. Today, UL certificates cover one steel door model, KYFD001S. For every other line we confirm the rating and documents per project.
Fire Rated Steel Doors
Steel doors and frames. Pair and unequal-pair availability to be confirmed.
UL certificates: model KYFD001S only
Fire Rated Wood Doors
Timber-faced fire doors for interior openings.
Rating confirmed per project
Stainless Steel Fire Doors
Stainless steel faces for hygienic or corrosive areas.
Rating confirmed per project
Fire Shutters
Steel and inorganic-fabric fire shutters for large openings.
Rating confirmed per project
Fire Rated Windows
Fixed and opening fire windows, series name if public.
Rating confirmed per project
Fire Rated Curtain Walls
Framing, glazing and design support for fire-rated sections.
Rating confirmed per project
Need a size, glazing or pair that falls outside a tested construction? We tell you before production and offer three routes: change to a covered construction, a project assessment, or a new test priced into the quote.
Not fire-rated: clean room and industrial doors
These doors are not fire-rated and carry no fire label. Use them where the opening has no fire-resistance requirement. For a fire-rated opening, see Fire Rated Steel Doors.
Clean Room Doors
Swing doors for clean rooms and controlled areas. Performance data with its test report.
Not fire-rated
Hermetic Sliding Doors
Sliding doors for airtight rooms. Airtightness class and test standard.
Not fire-rated
Traffic and Impact Doors
Swing doors for busy service routes. Leaf materials and impact protection options.
Not fire-rated
High Speed Roll Up Doors
PVC high-speed doors for logistics and process areas. Opening speed and wind class per report.
Not fire-rated
A fire door is the whole assembly, not just the leaf
A fire test burns the leaf, frame, hardware and seals together, fixed into one kind of wall. What protects the opening is everything installed in it, so we check each part against the evidence for your opening.
Door leaf
The part that swings. For KYFD001S, a single-swing, steel-covered composite leaf.
Frame
Fixed into the wall and carries the leaf. Frame profiles, steel gauge and fixing method per wall type.
Hardware
Hinges, locks and closers. Each item has to match the tested construction or be confirmed for the project.
Seals
Intumescent strips in the door gap and fire-rated sealant between frame and wall close the paths smoke and flame would take.
Wall
A door is only as good as the wall it is fixed into. The KYFD001S certificates cover masonry construction only.
Our UL certificates cover the KYFD001S door leaf in masonry walls. Frames, hardware and seals are confirmed per project against your drawings and the evidence your authority accepts.
What our UL certificates cover — and what they don't
Our UL certificates cover one door model. Below is exactly what they say, so you can check it against your opening before you ask for a quote.
| Model | Door | Wall | Rating | Standards | Certificate |
|---|---|---|---|---|---|
| KYFD001S | Single-swing, steel-covered composite door | Masonry construction | Up to and including 3 hours | UL 10B; CAN/ULC 104:2015 (R2025) | UL Certificate of Compliance R41930, Report Reference R41930-20251222, issued 25 Dec 2025 |
Not covered by these certificates
- Pairs and double-egress doors
- Door frames (the certificate covers the door leaf)
- Lightweight or gypsum partitions
- Any model other than KYFD001S
- Vision panels, louvres, transoms and sidelights
- Maximum door size — not stated on the certificate
Check it yourself: search UL Product iQ for Guangdong Jieyue Technology. For a matching project, we send the certificate copy on request. How to check, step by step
Before ordering, confirm size, handing, frame and certificate scope with us.
Straight answers
Are all your fire doors UL listed?
No. Our UL certificates cover one model, KYFD001S — a single-swing steel door for masonry walls, rated up to 3 hours. For other doors we confirm the rating and evidence per project, and tell you before production if an opening falls outside a tested construction.
Can you make doors to our opening sizes?
Single leaves up to the sizes listed for each product line, pairs on request. A size outside the certificate's scope is not covered by the certificate; we flag this per opening before production, never after delivery.
Can you supply projects in the Middle East?
For Middle East projects, the UL documents for KYFD001S are the starting point. Local civil defence approval is applied for per project, with the importer or contractor. Tell us the country and approving authority before tender and we confirm which documents apply.
Can a clean room or hermetic door be used as a fire door?
No. Our clean room, hermetic sliding, traffic and high-speed doors are not fire-rated. If an opening needs a fire rating, it needs a fire-rated door assembly.
How the doors are made and checked
Doors are produced by our manufacturing partner in Foshan, Guangdong.Each door is checked before dispatch for dimensions, finish, opening and closing, seals and hardware fit.

Metal-faced door leaves stacked on a trolley for delivery 
Wood-grain finished door leaves awaiting packing
Documents for your submittal
Public
Certificate numbers and scope for KYFD001S, and how to check them yourself.
On request
Certificate copies for a matching project. Tell us the country, standard and openings first.
Per project
A document list for each opening in your schedule: which certificate covers it, or a note that none does.
Send your door schedule
A useful quote depends on more than a unit price: the door schedule, rating per opening, frames, hardware, glazing, finish, documents, packing and destination. Send what you have — schedule, drawings or photos in PDF, Excel or Word — and mark what is still open.
We reply within N working days.